ecosmak.ru

A device for checking a fire pump for leaks. Centrifugal pump test

Operation and maintenance of fire truck pumps is carried out in accordance with the “Manual for the Operation of Firefighting Equipment”, manufacturer’s instructions for fire trucks, fire pump certificates and other regulatory documents. centrifugal fire pump

When receiving fire trucks, it is necessary to check the integrity of the seals on the pump compartment. Before deployment to a combat crew, it is necessary to run-in the pumps when operating on open water sources. The geometric suction height when running pumps should not exceed 1.5 m. The suction line should be laid on two hoses with a suction mesh. Two pressure hose lines with a diameter of 66 mm should be laid from the pump, each for one hose 20 m long. Water is supplied through RS-70 trunks with a nozzle diameter of 19 mm.

When running in, the pressure on the pump must be maintained at no more than 50 m. The pump is run in for 10 hours. When running in pumps and installing them on fire reservoirs, it is not allowed to direct the barrels and jets of water into the reservoir. Otherwise, small bubbles form in the water, which enter the pump through the mesh and suction line and thereby contribute to the occurrence of cavitation. In addition, the pump parameters (pressure and flow), even without cavitation, will be lower than under normal operating conditions.

Run-in of pumps after a major overhaul is also carried out within 10 hours and in the same mode, after a routine repair - within 5 hours. During the run-in, it is necessary to monitor the readings of instruments (tachometer, pressure gauge, vacuum gauge) and the temperature of the pump housing at the location where the bearings are installed. and seals. After every 1 hour of pump operation, it is necessary to turn the oiler 2...3 turns to lubricate the seals. Before running in, the oiler must be filled with a special lubricant, and transmission oil must be poured into the space between the front and rear bearings.

The purpose of running-in is not only to break in the parts and elements of the transmission and fire pump, but also to check the functionality of the pump. If minor faults are found during running-in, they should be eliminated, and then further running-in should be carried out.

If defects are discovered during running-in or during the warranty period, it is necessary to draw up a complaint report and present it to the fire truck supplier. The procedure for submitting a complaint report to the supplier plant is set out in the “Manual on the operation of fire fighting equipment”. Before drawing up a complaint report for a major defect, you must call a representative of the supplier plant by telegram.

If a representative of the plant does not arrive within three days or notifies by telegram that it is impossible to arrive, a unilateral complaint report is drawn up with the participation of a specialist from a disinterested party. It is prohibited to disassemble the pump or other components in which a defect is found until a representative of the plant arrives or the plant receives a complaint report. The warranty period for fire truck pumps in accordance with OST 22-929-76 is 18 months from the date of receipt. The operating life of the PN-40UA pump before the first major overhaul according to the passport is 950 hours.

The running-in of pumps should end with testing them for pressure and flow at the rated speed of the pump shaft. It is convenient to carry out the test on special stands at the PA technical diagnostic station in technical service units (units). If there are no such stands in the fire brigade, then the test is carried out at the fire department. In accordance with OST 22-929-76, the reduction in pump pressure at rated flow and impeller rotation speed should not be more than 5% of the rated value for new pumps. The results of running in the pump and testing it are recorded in the fire truck log.

After running in and testing the fire pump, maintenance of pump No. 1 should be carried out. Particular attention must be paid to changing the oil in the pump housing and checking the fastening of the impeller. Every day, when changing the guard, the driver must check: - the cleanliness, serviceability and completeness of the components and assemblies of the pump and its communications by external inspection, the absence of foreign objects in the suction and pressure pipes of the pump; - operation of valves on the pressure manifold and water-foam communications; - the presence of grease in the stuffing box and oil in the pump housing; - lack of water in the pump; - serviceability of control devices on the pump; - illumination in the vacuum tap, lamp in the pump compartment lighting lamp; - pump and water-foam communications for “dry vacuum”.

To lubricate the oil seals, the oiler is filled with lubricants such as solidol-S or pressolidol-S, CIATI-201. To lubricate the ball bearings of the pump, general purpose transmission oils of the type: TAp-15 V, TSp-14 are poured into the housing. The oil level should match the mark on the dipstick. It is recommended to change the oil after 100...120 hours of pump operation.

When checking the pump for “dry vacuum”, it is necessary to close all taps and valves on the pump, turn on the engine and create a vacuum in the pump using a vacuum system of 73...36 kPa (0.73...0.76 kgf/cm2). The vacuum drop in the pump should be no more than 13 kPa (0.13 kgf/cm2) in 2.5 minutes. If the pump does not pass the vacuum test, it is necessary to pressure test the pump with air under a pressure of 200...300 kPa (2...3 kgf/cm2) or water under a pressure of 1200...1300 kPa (12...13 kgf/cm2 ). Before crimping, it is advisable to moisten the joints with a soap solution. To measure the vacuum in the pump, it is necessary to use an attached vacuum gauge with a connecting head or thread for installation on the suction pipe of the pump or a vacuum gauge installed on the pump. In this case, a plug is installed on the suction pipe.

When servicing pumps during a fire or during a training exercise, it is necessary to: place the machine on a water source so that the suction line is, if possible, on 1 sleeve, the bend of the sleeve is smoothly directed downward and begins directly behind the suction pipe of the pump (Fig. 4.32.); to turn on the pump when running the engine needs to squeeze the clutch, turn on the power take-off in the driver's cabin, and then turn off the clutch with the handle in the pump compartment; *immerse the suction mesh in water to a depth of at least 600 mm, make sure that the suction mesh does not touch the bottom of the reservoir; *check before drawing water that all valves and taps on the pump and water-foam communications are closed; *take water from the reservoir by turning on the vacuum system, for which do the following: - turn on the backlight, turn the handle of the vacuum valve towards you; - turn on the gas-jet vacuum apparatus; -increase the rotation speed using the “Gas” lever; - when water appears in the sight glass of the vacuum valve, close it by turning the handle; - use the “Gas” lever to reduce the rotation speed to idle speed; - smoothly engage the clutch using the lever in the pump compartment; - turn off the vacuum apparatus; - use the “Gas” lever to increase the pressure on the pump (according to the pressure gauge) to 30 m; - smoothly open the pressure valves, use the “Gas” lever to set the required pressure on the pump; -monitor instrument readings and possible malfunctions; - when working from fire reservoirs, pay special attention to monitoring the water level in the reservoir and the position of the suction mesh; - after every hour of pump operation, lubricate the oil seals by turning the oiler cap 2...3 turns; - after supplying foam using a foam mixer, rinse the pump and communications with water from a tank or water source; - it is recommended to fill the tank with water after a fire from the water source used only if you are sure that the water does not contain impurities; -after work, drain the water from the pump, close the valves, install plugs on the pipes.

When using pumps in winter, it is necessary to take measures against freezing of water in the pump and in the pressure fire hoses: - at temperatures below 0? C, turn on the heating system of the pump compartment and turn off the additional engine cooling system; - in case of a short-term interruption of water supply, do not turn off the pump drive, keep the pump speed low; - when the pump is running, close the pump compartment door and monitor the control devices through the window; - to prevent freezing of water in the sleeves, do not completely block the trunks; - disassemble the hose lines from the barrel to the pump without stopping the water supply (in small quantities); - when stopping the pump for a long time, drain the water from it; - before using the pump in winter after a long stay, turn the motor shaft and transmission onto the pump using the crank, making sure that the impeller is not frozen; - warm up frozen water in the pump and hose line connections hot water, steam (from special equipment) or exhaust gases from the engine. Maintenance No. 1 (TO-1) for a fire truck is carried out after 1000 km of total mileage (taking into account the above), but at least once a month.

The fire pump in front of TO-1 is subject to daily maintenance. TO-1 includes: - checking the fastening of the pump to the frame; - checking threaded connections; - checking the serviceability (if necessary, disassembling, lubrication and minor repairs or replacement) of taps, valves, control devices; - incomplete disassembly pump (removing the cover), checking the fastening of the impeller, keyed connection, eliminating clogging of the flow channels of the impeller; - changing the oil and refilling the oil seal; - checking the pump for “dry vacuum”; - testing the pump for intake and supply of water from an open water source.

Maintenance No. 2 (TO-2) for a fire truck is carried out every 5,000 km of total mileage, but at least once a year. TO-2, as a rule, is performed in technical service units (units) at special posts. Before carrying out TO-2, the vehicle, including the pumping unit, is diagnosed on special stands.

TO-2 includes performing the same operations as TO-1, and, in addition, provides for checking: - the correctness of the readings of control devices or their certification in special institutions; - the pressure and flow of the pump at the rated speed of the pump shaft at a special stand at the technical diagnostic station or using a simplified method with installation on an open water source and using pump control devices.

The pump flow is measured by water meter shafts or estimated approximately by the diameter of the nozzles on the barrels and the pressure at the pump. The pump pressure drop should be no more than 15% of the nominal value at rated flow and shaft speed; - tightness of the pump and water-foam communications on a special stand, followed by troubleshooting.

Rated by: 4 people

METHODOLOGICAL PLAN

conducting classes with the group of the duty guard of the 52nd fire department on Firefighting equipment.
Topic: “Fire pumps.” Type of lesson: class-group. Allotted time: 90 minutes.
Purpose of the lesson: consolidation and improvement of personal knowledge on the topic: “Fire pumps.”
1. Literature used during the lesson:
Textbook: “Fire fighting equipment” V.V. Terebnev. Book No. 1.
Order No. 630.

Definition and classification of pumps.

Pumps are machines that convert supplied energy into mechanical energy of the pumped liquid or gas. Pumps are used in fire fighting equipment various types(Fig. 4.6.) Mechanical pumps are most widely used, in which the mechanical energy of a solid, liquid or gas is converted into mechanical energy of a liquid.

According to the principle of operation, pumps are classified depending on the nature of the prevailing forces, under the influence of which the pumped medium moves in the pump.

There are three such forces:
mass force (inertia), fluid friction (viscosity) and surface pressure force.

Pumps in which the action of mass forces and fluid friction (or both) predominate are combined into a group of dynamic pumps in which surface pressure forces predominate, making up a group of positive displacement pumps. Requirements for pumping installations of fire trucks.

Fire truck pumps are powered by internal combustion engines - this is one of the main technical features that must be taken into account when developing and operating pumps. The following basic requirements apply to pumping units.

Fire truck pumps must operate from open water sources, so no cavitation phenomena should be observed at the control suction height. In our country, the control suction height is 3...3.5 m, in countries Western Europe – 1,5.

The pressure characteristic Q - H for fire pumps should be flat, otherwise when the valves on the trunks are closed (reducing the flow), the pressure on the pump and in the hose lines will increase sharply, which can lead to rupture of the hoses. With a flat pressure characteristic, it is easier to control the pump using the “gas” handle and change the pump parameters if necessary.

In terms of energy parameters, fire truck pumps must correspond to the parameters of the engine from which they operate, otherwise the technical capabilities of the pumps will not be fully realized or the engine will operate in a mode of low efficiency and high specific fuel consumption.

The pumping installations of some fire trucks (for example, airfield ones) must operate while moving when water is supplied from monitors. Vacuum systems of fire truck pumps must ensure water intake within a control time (40...50 s) from the maximum possible suction depth (7...7.5 m).

Stationary foam mixers on fire truck pumps must, within established limits, produce a dosage of foam concentrate when the foam barrels are operating.

Pumping installations of fire trucks must operate without reducing parameters long time when supplying water at low and high temperatures.

Pumps should be as small in size and weight as possible to rationally use the carrying capacity of the fire truck and its body.

Control of the pumping unit should be convenient, simple and, if possible, automated, with low level noise and vibration during operation. One of the important requirements for successful fire extinguishing is the reliability of the pumping unit.

The main structural elements of centrifugal pumps are the working parts, casing, shaft supports, and seal.

The working bodies are impellers, inlets and outlets.

Pump impeller normal pressure made of two disks - leading and covering.
Between the disks there are blades bent in the direction opposite to the direction of rotation of the wheel. Until 1983, the impeller blades had double curvature, which ensured minimal hydraulic losses and high cavitation properties.

However, due to the fact that the manufacture of such wheels is labor-intensive and they have significant roughness, modern fire pumps use impellers with cylindrical blades (PN-40UB, PN-110B, 160.01.35, PNK-40/3). The angle of installation of the blades at the outlet of the impeller is increased to 65...70?, the blades have an S-shape in plan.

This made it possible to increase the pump pressure by 25...30% and the flow rate by 25% while maintaining cavitation qualities and efficiency at approximately the same level.

The weight of the pumps has been reduced by 10%.

When pumps operate, a hydrodynamic axial force acts on the impeller, which is directed along the axis towards the suction pipe and tends to move the wheel along the axis, therefore important element The impeller is mounted in the pump.

The axial force arises due to the difference in pressure on the impeller, since from the side of the suction pipe there is less pressure acting on it than on the right.

The magnitude of the axial force is approximately determined by the formula
F = 0.6 R? (R21 – R2в),
where F – axial force, N;
P – pressure at the pump, N/m2 (Pa);
R1 – inlet radius, m;
Rв – shaft radius, m.

To reduce the axial forces acting on the impeller, holes are drilled in the drive disk through which liquid flows from the right side to the left. In this case, the amount of leakage is equal to leakage through the target seal behind the wheel, and the pump efficiency decreases.

As the target seal elements wear out, fluid leakage will increase and pump efficiency will decrease.

In two- and multi-stage pumps, impellers on the same shaft can be placed with the opposite direction of entry - this also compensates or reduces the effect of axial forces.

In addition to axial forces, radial forces act on the impeller during pump operation. The diagram of radial forces acting on the impeller of a pump with one outlet is shown in Fig. 4.21. The figure shows that an unevenly distributed load acts on the impeller and pump shaft during rotation.

In modern fire pumps, the shaft and impeller are unloaded from the action of radial forces by changing the design of the bends.

The outlets in most fire pumps are of the volute type. The pump 160.01.35 (standard brand) uses a blade-type outlet (guide vane), behind which there is an annular chamber. In this case, the effect of radial forces on the impeller and pump shaft is reduced to a minimum. Spiral bends in fire pumps are made with single (PN-40UA, PN-60) and double-spiral (PN-110, MP-1600).

In fire pumps with a single-scroll outlet, unloading from radial forces is not performed; it is absorbed by the pump shaft and bearings. In two-helix bends, the effect of radial forces in spiral bends is reduced and compensated.

The connections in fire centrifugal pumps are usually axial, made in the form of a cylindrical pipe. The pump 160.01.35 has a pre-connected auger. This helps to improve the cavitation properties of the pump.

The pump housing is the basic part; it is usually made of aluminum alloys.

The shape and design of the housing depends on design features pump

Shaft supports are used for built-in fire pumps. Shafts in most cases are mounted on two rolling bearings.

Design of centrifugal pumps. In our country, fire trucks are mainly equipped with normal pressure pumps of the type PN-40, 60 and 110, the parameters of which are regulated by OST 22-929-76. In addition to these pumps for heavy airfield vehicles on the MAZ-543 chassis,

MAZ-7310 uses pumps 160.01.35 (according to the drawing number).

Of the combined pumps on fire trucks, the PNK 40/3 brand pump is used.

A pump has currently been developed and is being prepared for release. high pressure NVD 20/300.

Fire pump PN-40UA.

The unified fire pump PN-40UA has been mass-produced since the early 80s instead of the PN-40U pump and has proven itself well in practice.

Modernized pump PN-40UA unlike PN-40U, it is made with a removable oil bath located in the rear part of the pump. This greatly facilitates pump repair and housing manufacturing technology (the housing is divided into two parts).
In addition, the PN-40UA pump uses new way fastening the impeller on two keys (instead of one), which increased the reliability of this connection.

Pump PN-40UA

is unified for most firefighting vehicles and is adapted for rear and middle placement on the chassis of GAZ, ZIL, Ural vehicles.

Pump PN-40UA The pump consists of a pump housing, a pressure manifold, a foam mixer (brand PS-5) and two valves. housing 6, cover 2, shaft 8, impeller 5, bearings 7, 9, sealing cup 13, tachometer worm drive 10, cuff 12, flange coupling 11, screw 14, plastic packing 15, hose 16.

The impeller 5 is secured to the shaft using two keys 1, a lock washer 4 and a nut 3.

The cover is secured to the pump body with studs and nuts; a rubber ring is installed to ensure sealing of the connection.

The gap seals (front and rear) between the impeller and the pump casing are made in the form of bronze O-rings (Br OTSS 6-6-3) on the impeller (press-fit) and cast iron rings in the pump casing.

The sealing rings in the pump housing are secured with screws.

The pump shaft is sealed using plastic packing or frame rubber seals, which are placed in a special sealing cup. The glass is bolted to the pump body through a rubber gasket.

The bolts are secured with wire through special holes to prevent them from unwinding.

When using plastic packing PL-2 in a shaft seal, it is possible to restore the sealing of the unit without this. This is done by pressing the packing with a screw.

When using ASK-45 frame oil seals to seal the pump shaft and replacing them, it is necessary to remember that of the four oil seals, one (the first one to the impeller) operates under vacuum and three operate under pressure. To distribute the lubricant, an oil distribution ring is provided in the stuffing box, which is connected by channels to a hose and a grease fitting.

The water collecting ring of the glass is connected by a channel to a drainage hole, abundant leakage of water from which indicates wear of the seals.

The cavity in the pump housing between the sealing cup and the flange coupling seal serves as an oil bath for lubricating the bearings and the tachometer drive.

Oil bath capacity 0.5 l Oil is poured through a special hole closed with a plug. The drain hole with plug is located at the bottom of the oil bath housing.

Water is drained from the pump by opening the tap located at the bottom of the pump housing. For ease of opening and closing the tap, its handle is extended with a lever. On the diffuser of the pump housing there is a collector (AL-9 aluminum alloy), to which a foam mixer and two valves are attached.

A pressure valve is mounted inside the collector to supply water to the tank (Fig. 4.26.). The manifold body has holes for connecting a vacuum valve, a pipeline to the coil of the additional engine cooling system, and a threaded hole for installing a pressure gauge.

Pressure valves are attached with pins to the pressure manifold. Valve 1 is cast from gray cast iron (SCh 15-32) and has an eye for a steel (StZ) axis 2, the ends of which are installed in the grooves of the housing 3 made of aluminum alloy AL-9. A rubber gasket is attached to the valve with screws and a steel disk. The valve closes the passage hole under the influence of its own weight.

Spindle 4 presses the valve to the seat or limits its travel if it is opened by water pressure from the fire pump.

Fire pump PN-60

centrifugal normal pressure, single-stage, cantilever. Without guide vane.

The PN-60 pump is geometrically similar to the PN-40U pump model, therefore it is not structurally different from it.

Pump housing 4, pump cover and impeller 5 are cast from cast iron. Fluid is removed from the wheel through a spiral single-helix chamber 3, ending with a diffuser 6.

Impeller 5 with an outer diameter of 360 mm is mounted on a shaft with a diameter of 38 mm at the landing site. The wheel is secured using two diametrically located keys, a washer and a nut.

The pump shaft is sealed with frame seals of the ASK-50 type (50 is the shaft diameter in mm). The seals are placed in a special glass. Oil seals are lubricated through an oil can.

To operate from an open water source, a water collector with two nozzles for suction hoses with a diameter of 125 mm is screwed onto the suction pipe of the pump.

The drain valve of the pump is located at the bottom of the pump and is directed vertically downwards (in the PN-40UA pump on the side).

Fire pump PN-110

centrifugal normal pressure, single-stage, cantilever, without a guide vane with two spiral outlets and pressure valves on them.

The main working parts of the PN-110 pump are also geometrically similar to the PN-40U pump.

The PN-110 pump has only a few design differences, which are discussed below.

Pump housing 3, cover 2, impeller 4, suction pipe 1 are made of cast iron (SCh 24-44).

The diameter of the pump impeller is 630 mm, the diameter of the shaft at the place where the oil seals are installed is 80 mm (ASK-80 oil seals). The drain valve is located at the bottom of the pump and is directed vertically downwards.

The diameter of the suction pipe is 200 mm, the pressure pipes are 100 mm.

The pressure valves of the PN-110 pump have design differences (Fig. 4.29).

The housing 7 contains a valve with a rubber gasket 4. The housing cover 8 contains a spindle with a thread 2 in the lower part and a handwheel

9. The spindle is sealed by stuffing box 1, which is sealed by a union nut.

When the spindle rotates, nut 3 moves progressively along the spindle. Two strips 6 are attached to the nut axles, which are connected to the axis of the valve 5 of the valve, so when the handwheel rotates, the valve opens or closes.

Combined fire pumps.

Combined fire pumps include those that can supply water under normal (pressure up to 100) and high pressure (pressure up to 300 m or more).

In the 80s, VNIIPO of the USSR Ministry of Internal Affairs developed and manufactured a pilot series of self-priming combined pumps PNK-40/2 (Fig. 4.30.). Water is sucked in and supplied under high pressure by a vortex stage, and under normal pressure by a centrifugal impeller. The vortex wheel and the impeller of the normal stage of the PNK-40/2 pump are placed on the same shaft and in the same housing.

The Priluki OKB of fire engines has developed a combined fire pump PNK-40/3, a pilot batch of which is being tested in fire protection garrisons.

Pump PNK-40/3

consists of a normal pressure pump 1, which in design and dimensions corresponds to the PN-40UA pump; gearbox 2, increasing speed (multiplier), high pressure pump (stage)

3. The high pressure pump has an open impeller. Water from the pressure manifold of the normal pressure pump is supplied through a special pipeline to the suction cavity of the high pressure pump and to the normal pressure pressure pipes. From the pressure pipe of the high-pressure pump, water is supplied through hoses to special pressure nozzles to produce a finely atomized jet.

Technical specifications pump PNK-40/3

Normal pressure pump:
feed, l/s................................................... ...................................40
pressure, m................................................... ..................................100
pump shaft rotation speed, rpm....................................2700
Efficiency................................................... ...........................................0.58
cavitation reserve................................................... ............... 3
power consumption (at rated mode), kW....67.7
High pressure pump (with sequential operation of pumps):
feed, l/s................................................... ...............................11.52
pressure, m................................................... ................................... 325
rotation speed, rpm................................................... ...... 6120
Overall efficiency................................................... ........................... 0.15
power consumption, kW................................... 67, 7

Combined operation of normal and high pressure pumps:
flow, l/s, pump:
normal pressure................................................... ........ 15
high pressure................................................ ............... 1.6
head, m:
normal pressure pump......................................................... 95
common for two pumps......................................................... ...... 325
Overall efficiency................................................... .................................... 0.27
Dimensions, mm:
length................................................. ...................................600
width................................................. ............................... 350
height................................................. ................................ 650
Weight, kg................................................... ..................................... 140

Basics of Centrifugal Pump Operation

Operation and maintenance of fire truck pumps is carried out in accordance with the “Manual for the Operation of Firefighting Equipment”, manufacturer’s instructions for fire trucks, fire pump certificates and other regulatory documents.

When receiving fire trucks, it is necessary to check the integrity of the seals on the pump compartment.

Before deployment to a combat crew, it is necessary to run-in the pumps when operating on open water sources.

The geometric suction height when running pumps should not exceed 1.5 m. The suction line should be laid on two hoses with a suction mesh. Two pressure hose lines with a diameter of 66 mm should be laid from the pump, each for one hose 20 m long. Water is supplied through RS-70 trunks with a nozzle diameter of 19 mm.

When running in, the pressure on the pump must be maintained at no more than 50 m. The pump is run in for 10 hours. When running in pumps and installing them on fire reservoirs, it is not allowed to direct the barrels and jets of water into the reservoir.

Otherwise, small bubbles form in the water, which enter the pump through the mesh and suction line and thereby contribute to the occurrence of cavitation. In addition, the pump parameters (pressure and flow), even without cavitation, will be lower than under normal operating conditions.

Run-in of pumps after a major overhaul is also carried out for 10 hours and in the same mode, after routine repairs - for 5 hours.

During break-in, it is necessary to monitor the readings of instruments (tachometer, pressure gauge, vacuum gauge) and the temperature of the pump housing at the location where the bearings and seals are installed.

After every 1 hour of pump operation, it is necessary to turn the oiler 2...3 turns to lubricate the seals.

Before running in, the oiler must be filled with a special lubricant, and transmission oil must be poured into the space between the front and rear bearings.

The purpose of running-in is not only to break in the parts and elements of the transmission and fire pump, but also to check the functionality of the pump. If minor faults are found during running-in, they should be eliminated, and then further running-in should be carried out.

If defects are discovered during running-in or during the warranty period, it is necessary to draw up a complaint report and present it to the fire truck supplier.

If a representative of the plant does not arrive within three days or notifies by telegram that it is impossible to arrive, a unilateral complaint report is drawn up with the participation of a specialist from a disinterested party. It is prohibited to disassemble the pump or other components in which a defect is found until a representative of the plant arrives or the plant receives a complaint report.

The warranty period for fire truck pumps in accordance with OST 22-929-76 is 18 months from the date of receipt. The service life of the PN-40UA pump before the first major overhaul according to the passport is 950 hours.

The running-in of pumps should end with testing them for pressure and flow at the rated speed of the pump shaft. It is convenient to carry out the test on special stands at the PA technical diagnostic station in technical service units (units).

If there are no such stands in the fire brigade, then the test is carried out at the fire department.

In accordance with OST 22-929-76, the reduction in pump pressure at rated flow and impeller rotation speed should not be more than 5% of the rated value for new pumps.

The results of running in the pump and testing it are recorded in the fire truck log.

After running in and testing the fire pump, maintenance of pump No. 1 should be carried out. Particular attention must be paid to changing the oil in the pump housing and checking the fastening of the impeller.

Every day when changing the guard, the driver must check:
- cleanliness, serviceability and completeness of the components and assemblies of the pump and its communications by external inspection, the absence of foreign objects in the suction and pressure pipes of the pump;
- operation of valves on the pressure manifold and water-foam communications;
- the presence of grease in the stuffing box and oil in the pump housing;
- lack of water in the pump;
- serviceability of control devices on the pump;
- illumination in the vacuum tap, lamp in the pump compartment lighting lamp;
- pump and water-foam communications for “dry vacuum”.

To lubricate the oil seals, the oiler is filled with lubricants such as solidol-S or pressolidol-S, CIATI-201. To lubricate the ball bearings of the pump, general purpose transmission oils of the type: TAp-15 V, TSp-14 are poured into the housing.

The oil level should match the mark on the dipstick.

When checking the pump for “dry vacuum”, it is necessary to close all taps and valves on the pump, turn on the engine and create a vacuum in the pump using a vacuum system of 73...36 kPa (0.73...0.76 kgf/cm2).

The vacuum drop in the pump should be no more than 13 kPa (0.13 kgf/cm2) in 2.5 minutes.

If the pump does not pass the vacuum test, it is necessary to pressure test the pump with air under a pressure of 200...300 kPa (2...3 kgf/cm2) or water under a pressure of 1200...1300 kPa (12...13 kgf/cm2 ). Before crimping, it is advisable to moisten the joints with a soap solution.

To measure the vacuum in the pump, it is necessary to use an attached vacuum gauge with a connecting head or thread for installation on the suction pipe of the pump or a vacuum gauge installed on the pump. In this case, a plug is installed on the suction pipe.

When servicing pumps during a fire or drill, you must:
place the machine on a water source so that the suction line is, if possible, on 1 sleeve, the bend of the sleeve is smoothly directed downward and begins directly behind the suction pipe of the pump (Fig. 4.32.);
to turn on the pump while the engine is running, it is necessary to depress the clutch, turn on the power take-off in the driver's cabin, and then disengage the clutch with the handle in the pump compartment;
*immerse the suction mesh in water to a depth of at least 600 mm, make sure that the suction mesh does not touch the bottom of the reservoir;
*check before drawing water that all valves and taps on the pump and water-foam communications are closed;
*take water from the reservoir by turning on the vacuum system, for which do the following work:
- turn on the backlight, turn the vacuum valve handle towards you;
- turn on the gas-jet vacuum apparatus;
-increase the rotation speed using the “Gas” lever;
- when water appears in the sight glass of the vacuum valve, close it by turning the handle;
- use the “Gas” lever to reduce the rotation speed to idle speed;
- smoothly engage the clutch using the lever in the pump compartment;
- turn off the vacuum apparatus;
- use the “Gas” lever to increase the pressure on the pump (according to the pressure gauge) to 30 m;
- smoothly open the pressure valves, use the “Gas” lever to set the required pressure on the pump;
-monitor instrument readings and possible malfunctions;
- when working from fire reservoirs, pay special attention to monitoring the water level in the reservoir and the position of the suction mesh;
- after every hour of pump operation, lubricate the oil seals by turning the oiler cap 2...3 turns;
- after supplying foam using a foam mixer, rinse the pump and communications with water from a tank or water source;
- it is recommended to fill the tank with water after a fire from the water source used only if you are sure that the water does not contain impurities;
-after work, drain the water from the pump, close the valves, install plugs on the pipes.

When using pumps in winter, it is necessary to take measures against freezing of water in the pump and in the pressure fire hoses:
- at temperatures below 0? C turn on the heating system of the pump compartment and turn off the additional engine cooling system;
- in case of a short-term interruption of water supply, do not turn off the pump drive, keep the pump speed low;
- when the pump is running, close the pump compartment door and monitor the control devices through the window;
- to prevent freezing of water in the sleeves, do not completely block the trunks;
- disassemble the hose lines from the barrel to the pump without stopping the water supply (in small quantities);
- when stopping the pump for a long time, drain the water from it;
- before using the pump in winter after a long stay, turn the motor shaft and transmission onto the pump using the crank, making sure that the impeller is not frozen;
- warm up frozen water in the pump and hose line connections with hot water, steam (from special equipment) or exhaust gases from the engine.

Maintenance No. 1 (TO-1) for a fire truck is carried out after 1000 km of total mileage (taking into account the above), but at least once a month.

The fire pump in front of TO-1 is subject to daily maintenance. TO-1 includes:
- checking the fastening of the pump to the frame;
- checking threaded connections;
- checking the serviceability (if necessary, disassembling, lubrication and minor repairs or replacement) of taps, valves, control devices;
- partial disassembly of the pump (removing the cover), checking the fastening of the impeller, key connection, eliminating clogging of the flow channels of the impeller;
- changing the oil and refilling the oil seal;
- checking the pump for “dry vacuum”;
- testing the pump for intake and supply of water from an open water source.

Maintenance No. 2 (TO-2) for a fire truck is carried out every 5,000 km of total mileage, but at least once a year.

TO-2, as a rule, is performed in technical service units (units) at special posts. Before carrying out TO-2, the vehicle, including the pumping unit, is diagnosed on special stands.

TO-2 includes performing the same operations as TO-1, and, in addition, provides for checking:
- the correctness of the readings of control devices or their certification in special institutions;
- pressure and flow of the pump at the rated speed of the pump shaft on a special stand at a technical diagnostic station or using a simplified method with installation on an open water source and using pump control devices.

The pump flow is measured by water meter shafts or estimated approximately by the diameter of the nozzles on the barrels and the pressure at the pump.

The pump pressure drop should be no more than 15% of the rated value at rated flow and shaft speed;
- tightness of the pump and water-foam communications on a special stand with subsequent troubleshooting.

Pumps of fire trucks and motor pumps are tested during each maintenance No. 2 (after a run of 5000 km, but at least once a year) according to the methodology set out in the Manual on the technical service of the State Fire Service. The following conditions must be met during testing:

before starting the tests, it is necessary to check that the installation of pumps and pipelines were carried out in accordance with the requirements of the accompanying technical documentation for the fire truck;

valves, gate valves, and drain valves for water and foam communications of a fire truck must be in good condition and easy to close and open. The serviceability of the pump seal lubrication system is checked. Leaks at connections and controls are not allowed;

the shaft rotation speed of fire truck pumps should not exceed the nominal (specified in the technical documentation) by more than 5%;

the head pressure in the suction pipe of the pumps should not exceed 4.0 kg s/cm2 (0.4 MPa), and for pumps with a shaft seal with plastic packing 8.0 kg s/cm2 (0.8 MPa);

the pressure at the outlet of the fire truck pump should not be more than 11.0 kgf/cm2 (1.1 MPa);

tightness with a rotating impeller is checked by hydraulic pressure created by the pump itself at rated speed;

The start-up of pumps on fire trucks and motor pumps must be carried out with the valves on the pressure pipes completely closed;

the pumps of fire trucks equipped with a gas-jet vacuum system are started only after water appears in the vacuum tap;

If a malfunction is detected during the inspection period, the fire truck pump is immediately turned off. Further tests are carried out after troubleshooting.

Fire trunks, fire columns, branches, adapters, water collectors, etc.

The strength and tightness of the housings of the specified equipment must be ensured at a hydraulic pressure 1.5 times higher than the working pressure, and the tightness of the connections at the working pressure. At the same time, the appearance of traces of water in the form of drops on the outer surfaces of parts and at joints is not allowed.

The frequency of such tests is carried out once a year.

Personal respiratory and vision protection equipment

RPE is tested (checked) within the time limits according to the methodology established by the Manual on the gas and smoke protection service of the State Fire Service.

Fire protective suits

Fire protective suits are tested (checked) within the time limits and according to the methodology established by the manufacturer and the operating instructions.

Manual fire escapes

Manual fire escapes should be tested once a year and after each repair. Before using them in competitions, certificates are submitted for them. The use of manual fire escapes that have malfunctions, damage to main parts or have not passed the test is not permitted.

During testing, a retractable ladder is placed on solid ground, extended to its full height and leaned against a wall at an angle of 75° to the horizontal (2.8 m from the wall to the ladder shoes). In this position, each knee is loaded in the middle with a load of 100 kg for 2 minutes. The rope must withstand a tension of 200 kg without deformation.

After testing, the retractable ladder should not be damaged and the elbows should extend and lower without binding.

The specifics of admitting manual fire escapes to PPP competitions are stipulated by the Rules for holding PSP competitions.

When testing, the assault ladder is suspended freely by the end of the hook and each string at the level of the 2nd step from below is loaded with a load of 80 kg (160 kg in total) for 2 minutes. After testing, the assault ladder should have no cracks or residual deformation of the hook.

When testing, a stick ladder is installed on solid ground, leaned at an angle of 75° to the horizontal and loaded in the middle with a load of 120 kg for 2 minutes. After removing the load, the ladder-stick should not have any damage and should fold easily and tightly.

To test manual fire escapes, a dynamometer can be used instead of hanging a load.

After complete completion of all installation work, installation of the necessary instrumentation, automation, lubrication systems, ventilation devices and the floor of the top covering, a trial run and testing of the pump unit begins.

Before start-up, check the tightening of fastening bolts, threaded connections and seals. Check the lubrication in the system and remove dirt deposits and dust with compressed air. Clean, fresh oil is poured into the crankcase, clutches and gearbox. Manually rotate the clutch, while controlling the smoothness of rotation and the absence of jerking. If the unit is designed to supply hot substances, then before starting it is necessary to warm up the pump with steam with a temperature of at least 40°C from the pumped liquid. The valve located on the pressure pipeline regulates the performance and pressure of the unit's fluid. The first start-up of the pump must be carried out at low load.

The sequence of operations for starting centrifugal pumps is as follows:

  • Close all existing valves and taps on all pipelines and instrumentation, except for the valve on the suction pipeline, which can be closed to a maximum of 80%;
  • Open the taps to the cooler, oil seals and bearings to supply lubricant to them;
  • Open the air outlet valve. Fill the pump and suction pipeline with working fluid;
  • Close the air outlet valve. If there is a bypass, open it;
  • Start the engine and open the pressure gauge valves;

ATTENTION! It is prohibited to start pumps with the cooling system turned off and not filled with working fluid. It is prohibited to operate the pump for more than 2-3 minutes with the pressure pipeline valve closed.

  • When the required shaft rotation speed and nominal pressure on the pressure pipeline are reached, the valve of the pressure pipeline is opened. It is necessary to open it gradually in order to minimize the passage of liquid, thereby avoiding overheating of the engine and pump. If there is a bypass, then it is shut off;
  • By monitoring the uniform increase in the load on the engine using instrumentation, open the valve on the pressure pipeline to the operating value.

ATTENTION! If an overload occurs, you must immediately turn off the unit, identify and eliminate the causes of the malfunction.

  • To stop, slowly close the valve on the suction pipeline, then on the pressure pipeline and turn off the electric motor.

During operation, it is necessary to monitor the instrument readings. Resistance in the supply line, due to a valve that is not fully open or a blockage, can lead to an increase in pressure.

A uniform oscillation of the instrument needles, except for the voltmeter, indicates normal operation. In case of air leaks in the system, observed sharp jumps instrument arrow. In this case, it is necessary to check the tightness of the connections.

Malfunctions in the pump, as a rule, lead to an increase in the current consumed by the motor.

If knocking or overheating of the pump occurs, it is necessary to stop the unit, identify and eliminate faults.

During a trial run, the test must be controlled:

  • Noises and knocks;
  • Leaks of working fluid;
  • Coolant and lubricant leaks;
  • Bearing lubrication and temperature;
  • The oil temperature should not exceed 60°C;
  • The temperature of rubbing parts and bearings should be no more than 65°C.

The test is considered successfully completed if the pumping unit has operated smoothly and steadily for 2 hours. Next, industrial tests are carried out for 4 hours at full operating load.

List of generally accepted abbreviations (explanations):

  • PA - fire truck;
  • GVA is a gas-jet vacuum device designed to create a vacuum in the cavity of a centrifugal pump when drawing water from an open water source. It operates using the energy of exhaust gases from an internal combustion engine, directed instead of a PA muffler to a gas-jet pump, the vacuum chamber of which is connected by pipelines to the cavity of a centrifugal pump;
  • PN - fire pump;
  • Gearbox - gearbox;
  • PTO - power take-off, designed to transmit torque from the gearbox input shaft to the PN, activated in the driver's cab by a separate lever. Attached to the gearbox instead of the top cover.
  • G-600 - hydraulic elevator, designed for collecting water from hard-to-reach water sources and cleaning up excessively spilled water after extinguishing fires, is a water-jet pump;
  • PS - foam mixer. On pumps of the PN-40 series, a foam mixer of the PS-5 brand is installed (provides 1-5 foam generators GPS-600), designed for introducing a foaming agent into the water flow at a concentration of 4-6%, located between the pressure manifold and the suction pipe PN, has in its design water-jet pump and dispenser, can take foam concentrate both from the PA foam tank and from an external container;
  • vacuum valve, found in the literature under the name vacuum tap, vacuum shutter, designed to connect and disconnect the cavity of a centrifugal pump with a GVA vacuum chamber, installed on the PN pressure manifold;
  • pressure gauge - a device for measuring pressure, installed on the pressure manifold PN, calibrated in kgf/cm2;
  • pressure vacuum gauge - a device for measuring pressure, both positive and negative, installed on the suction pipe PN, calibrated in kgf/cm2;
  • drain faucet - a plug-type faucet, installed in the lower part of the PN housing to drain water after work, in addition, installed on the pipelines of the additional cooling system of the PA engine;
  • tachometer - a device for measuring the number of revolutions of the PN shaft, calibrated in revolutions per minute (rpm), there are mechanical and electrically driven.

Fire pump

Preparing a fire truck for work

When preparing a PA upon arrival at the place of work, you must:

  1. Set the PA to the handbrake;
  2. Install wheel chocks under the wheels.
  3. Attach the necessary hose lines;
  4. Set the gearbox lever to neutral position;
  5. Turn on the ignition by turning the key to the right until it clicks;
  6. Turn on the starter and start the engine.
  7. Press the clutch pedal and engage the PTO (to do this, move the gearbox lever towards you and smoothly release the clutch pedal);

Further operations to start the pump depend on operating conditions (water supply from a tank, open reservoir or hydrant). To avoid failure of the clutch release bearing, prolonged operation of the power transmission with the clutch depressed is not allowed.

Checking the fire pump for leaks

When testing a fire pump for leaks:

  1. Make sure there is no water in the pump. (If there is water in the pump cavity, intense vaporization is possible in a deep vacuum, as a result of which the creation of a vacuum is impossible). Drain the water through the pump drain cock with the vacuum valve open.
  2. Start the engine.
  3. Check the tightness of the closure of the drain valve, valves on the pressure pipes, pipes of the foam tank and additional cooling, valves from the tank and into the tank.
  4. Turn the handle of the vacuum valve to the “toward” position until it stops. (In this case, the cam of the vacuum valve shaft will press on the rod of the lower valve, which will lead to the connection of the pump cavity through the pipeline with the vacuum chamber of the GVA).
  5. Enable GVA. (The valve in the gas distribution mechanism will change its position, open the gas outlet hole into the gas jet vacuum apparatus and close the gas outlet hole into the muffler).
  6. Use the throttle control lever to increase engine speed to maximum. (When passing large quantity exhaust gases through the nozzle, vacuum chamber and GVA diffuser, a vacuum is created in the vacuum chamber and in the cavity of the pump).
  7. When the gauge needle (see Fig. 1) moves from “0” to 34 between 0 and -1 (which corresponds to 550 -570 mm Hg), Not When releasing gas, turn off the vacuum valve.
  8. Reduce engine speed. (At high engine speeds, the exhaust gases press the valve closing the muffler opening so hard that it is impossible to turn off the HVAC).
  9. Turn off GVA.
  10. Check the readings of the arrow on the pressure-vacuum gauge. If the vacuum changes by more than 100 mmHg within 2.5 minutes. the pump is considered leaky.

Rice. 1. Pressure and vacuum gauge readings when testing the pump for “dry vacuum”. Scale divisions from 0 to -1 are shown conventionally.

Additional explanations:

  1. When checking the pump, you should pay attention to the fact that the time required to create the required vacuum should not exceed 20 seconds. The reason for the slow creation of vacuum in the pump cavity may be a decrease in the flow area of ​​the vacuum system due to its clogging or incomplete opening of the vacuum shutter valve due to wear of the cam and valve stem.
  2. Vacuum gauges used on fire pumps do not have graduations such as 550 mmHg. and 100 mm Hg. Art. Division “-1” corresponds to -760 mm Hg. Art., or -10 m. water. Art. Taking this into account, the vacuum is brought to 3/4 of the scale to the left of zero. This will correspond to 550 mm Hg.

To determine the causes of vacuum system malfunctions, you can use the following techniques:

  • make sure that the pressure-vacuum gauge is working properly. For example, replace it with a known good one (that has passed verification) or test it on another pump.
  • Pressurize the pump with water from another pump with a pressure of 8 - 10 kg/cm2. Inspect the pressure pump and repair the leak. If the pump is sealed, then it is necessary to check the tightness of the vacuum system. Create a pressure of 4 - 7 atmospheres with the pump, open the vacuum valve. Inspect the vacuum system. There should be no leaks at the connection points and along the length of the pipeline.
  • Check the serviceability of the valve of the gas distribution mechanism; gases should not pass into the siren and into the muffler when the GVA is running.
  • The state of the flow section of the pipelines is determined by the amount of water leaving the GVA diffuser when it is supplied under pressure through an open vacuum valve.

Working with a pump without installing a PA on a reservoir

(Water supply from tank)

  1. Connect the hose lines to the pressure pipes (in this case, you should strive to keep the number of bends when laying the hoses to a minimum).
  2. Using a wrench, check the tightness of the plug on the suction pipe of the pump, as well as valves, gate valves and taps.
  3. Open the vacuum valve to allow air to escape from the cavity of the fire pump. (An air lock at the top of the pump cavity prevents water from filling the pump.)
  4. Open the tank valve. After water appears in the sight glass of the vacuum valve or from the GVA diffuser, close the vacuum valve.
  5. Engage the clutch and increase the speed until the pressure on the pressure gauge is 2 - 3 kgf/cm2.
  6. Smoothly open the valve in the hose line.
  7. Slowly add gas and bring the pressure to the required value.

Operations upon completion of work:

  1. Reduce engine speed to minimum.
  2. Disengage the clutch.
  3. Close the water supply valve to the pressure line.
  4. Close the water supply valve from the tank.
  5. Turn off the PTO and the car engine.
  6. Open the drain valve from the pump and the vacuum valve.
  7. Disconnect the hose lines.
  8. Place plugs on the pressure and suction pipes.
  9. Clean the hoses and hose equipment from dirt and place them in place with mandatory fastening.
  10. Close the compartments securely.

Upon arrival at the garage you should:

  1. Replace wet sleeves with a second set, and rinse and dry used ones.
  2. Refill the tank with fuel.
  3. Fill the oil can to lubricate the pump seals and check the oil level in the pump crankcase.
  4. Wash the car thoroughly, clean it of dirt, put the equipment in order.

Typical mistakes when performing the exercise.

  1. An attempt was made to supply water to the line without first filling the pump with water. (The presence of air in the pump cavity can lead to a delay in the supply of water to extinguish the fire, making it impossible to create the required pressure).
  2. Air release through vacuum - valve when the pump is turned on.
  3. Turning the pump on and off at high engine speeds.

Taking water from a reservoir

  1. Lower the sleeves with the mesh into the pond. The suction mesh must be lowered at least 300 mm below the water level (to avoid air leaks), but not to the bottom of the reservoir.
  2. Check the closure of the drain valve, all valves, valves and taps.
  3. (Rotation of the pump shaft when creating a vacuum in the pump cavity is unacceptable).
  4. Open the vacuum valve “pull” and turn on the illumination of the inspection window.
  5. Turn on the gas jet vacuum apparatus.
  6. Use the throttle lever to increase engine speed to maximum. (The characteristic noise of a working HVAC can be heard).
  7. When water appears in the viewing window (you can also be guided by the change in the sound of the operating HVAC), wait a short time until the air bubbles stop escaping, then close the vacuum valve (pull-away position).
  8. Engage clutch.
  9. Turn off GVA.
  10. Using the throttle lever, set the water pressure on the pressure gauge to 2-3 kgf/cm.
  11. Smoothly increase the pressure to the required value.
  12. If necessary, turn on additional cooling of the engine, and first open the drain valve on the pipeline connected to the suction cavity, then open the valve on the pipeline from the pressure cavity of the pump, when water appears from the open drain valve on the pipeline, close it, and open the valve on the pipeline connected to suction cavity. (This operation will prevent air from entering the additional cooling system into the pump cavity).

Typical errors during operation.

  1. Insufficient engine speed during HVAC operation.
  2. Reduce rotation speed until the vacuum valve closes.
  3. High pressure when opening pressure valves.
  4. Premature closing of the vacuum valve.
  5. Attempts to turn on and off the HVAC at high engine speeds.
  6. Engaging and disengaging the clutch at high engine speeds.

Additions and clarifications.

  1. After water appears in the inspection window, it is recommended to move the vacuum valve handle to the “away” position at any time of the year in order to purge the vacuum system of water.
  2. With low water pressure in the pump, it is easier to open the pressure valves and there is less chance of a water column breaking.
  3. When working with one hose line, it is more convenient to connect it to the left branch pipe, because control levers are located on the left.
  4. The suction line along its entire length must have a slope towards the reservoir. If in some place it turns out to be raised as a result of being laid through obstacles (bridge railings, reservoir hatch, etc.), then an air plug remains at the upper bend point of the sleeve. When water is introduced into the line, it can cause the water column to break or cause the pump to operate unstably for some time. This must be anticipated in advance when installing the car.

Taking water from a reservoir with a faulty vacuum system

  1. Place the car near a pond in compliance with safety measures.
  2. Attach the suction arms and suction mesh.
  3. Check the closure of the drain cock, all gate valves, valves and the plug valve of the foam mixer.
  4. Turn on the power take-off.
  5. Disconnect the clutch from the pump compartment.
  6. Open the vacuum valve “towards you” and turn on the illumination of the inspection eye.
  7. Open the “out of the tank” valve.
  8. When water appears in the sight glass, wait until the release of air bubbles stops and close the vacuum valve.
  9. Engage clutch.
  10. With a pen throttle valves set the water pressure to 1 - 1.5 kgf/cm2 using the pressure gauge.
  11. Smoothly open the pressure valve.
  12. Carry out activities upon completion of work and arrival at the garage.

Fire truck vacuum system diagram

Vacuum system of a fire truck: 1- body of a gas-jet vacuum apparatus; 2- engine exhaust pipe; 3 — siren resonator (if the siren is gas-jet); 4- dampers; 5‑pipeline; 6 — hole for purging the system after work; 7- vacuum valve body; 8‑cam roller (eccentric); 9- viewing peephole; 10- valve; 11- diffuser; 12 – nozzle; 13‑socket and light bulb.

Note. The position of the lever is in position 1a for purging the vacuum system in winter time; position in position 2a to create a vacuum in the cavity of the fire pump.

Typical errors during operation:

  1. An attempt was made to fill the suction line when the suction strainer valve is not closed.
  2. Untimely closing of the tank valve.
  3. Filling the suction line while the pump is running.
  1. The likelihood of a water column breaking is reduced if the valve from the tank is closed after water is supplied to the line.
  2. When filling the suction line, the suction strainer valve must be securely closed.

If this condition cannot be met, water can be collected by ringing the tank for which:

  1. Close all valves and drain cock;
  2. Engage clutch;
  3. Open the valve “out of the tank” completely and the valve “into the tank” ¾ of the way;
  4. Set the average speed of the pump shaft (2000-1500 rpm according to the tachometer). After filling the suction line and pump with water, the pressure on the pressure gauge will increase sharply and the sound of the engine will change;
  5. Smoothly open the pressure pipe valve;
  6. Close the “out of the tank” and “into the tank” valves;
  7. Set the required pressure.

Filling a tank with water from an open water source

This exercise differs from the usual supply only in that instead of a valve on the pressure pipe, a valve “into the tank” is opened.

However, it must be remembered that internal area the walls of the AC-40 (130) 63B tank truck is 10 m 2. With such an area, even a slight excess pressure (0.5 kgf/cm2) creates a breaking force of 5000 kg.

In order not to rupture the tank, it should be filled under low pressure of 1.5-2 atm. In this case, the control tube has time to pass excess water when the tank overflows.

When water appears from the control tube, the gas is immediately reduced and the clutch is engaged. After this, the valve “to the tank” is closed.

If it is necessary to speed up the filling of the tank, it is necessary to open the lid of the top hatch of the tank and only then increase the pressure. In addition, the initial opening of the valve “into the tank” must be done at minimum pressure.

Water supply

Water supply by fire tankers from a reservoir using a hydraulic elevator

A hydraulic elevator ring for supplying water from a reservoir can be constructed according to the following schemes:

  1. Pump - hydraulic elevator - pump.
  2. Pump - hydraulic elevator - branching - pump.
  3. Pump - hydraulic elevator - tank - pump.

In addition, the hydraulic elevator can be used to remove water from premises by installing the car on a water source.

Starting the hydraulic elevator according to the scheme: “pump-hydraulic elevator-pump”.


Rice. 2. Work according to the “Pump - hydraulic elevator - pump” scheme.

  1. Close all taps, valves and valves.
  2. Open the tank valve.
  3. Engage clutch.
  4. When the hose suitable for the water collector of the suction pipe is filled with water, wait some time until the pump operation stabilizes. (The inevitable, with this scheme, air entering the pump cavity makes it difficult to create a closed ring of water in the system. The air will come out through the hydraulic elevator after some time).
  5. Close the “out of tank” valve.

Starting the hydraulic elevator according to the scheme: “pump - hydraulic elevator - branching - pump”.

  1. Install the tanker at the work site, connect the hoses, branch, hydraulic elevator and trunk.

Check the connections for correctness and eliminate any sharp bends on the sleeves.


Rice. 3. “Working with a hydraulic elevator according to the pump - hydraulic elevator - branching - pump scheme.”

  1. Turn on the PTO and disengage the clutch from the pump compartment.
  2. Open the tank valve.
  3. Release the air from the pump cavity through the vacuum valve, and then close it.
  4. Engage clutch.
  5. Fully open the valve in the hydraulic elevator pressure line.
  6. Increase the pump shaft rotation speed to 2000-2500 rpm.
  7. When the hose suitable for the branch is filled with water, slightly open one of the side valves of the branch to release air, and then close it.
  8. Fully open the central branch valve that supplies water to the pump.
  9. Close the “out of the tank” valve.
  10. If necessary, adjust the pump shaft rotation speed, bringing it to 2000-2500 rpm. (At such speeds, the pressure in the suction cavity will be at least 2 - 4 kgf/cm2).
  11. Smoothly open the pressure valve to the barrel, making sure that the pressure in the suction cavity of the pump does not fall below 0.5 kgf/cm2.

Starting the hydraulic elevator according to the “pump - hydraulic elevator - tank - pump” scheme

  1. Install the tanker at the work site, connect the hoses, hydraulic elevator and barrel.

Check the connections for correctness and eliminate any sharp bends on the sleeves. Use pressure-suction hoses lowered into the tank to avoid kinks (see Fig. 4.).


Rice. 4. “Working with a hydraulic elevator according to the pump - hydraulic elevator - tank - pump scheme.”

  1. Close all taps and valves.
  2. Turn on the PTO and disengage the clutch from the pump compartment.
  3. Open the tank valve.
  4. Release the air from the pump cavity through the vacuum valve, and then close it.
  5. Fully open the valve in the hydraulic elevator pressure line.
  6. Engage clutch.
  7. Increase the pump shaft rotation speed to 2000-2500 rpm.

When the water returns to the tank

  1. Fully open the valve into the pressure line of the barrel.
  2. Set the water pressure on the pressure gauge to 8 kgf/cm2.
  3. Monitor the water level in the tank: when it decreases, close the pressure valve to the barrel, and when it increases, open it more and slightly reduce the speed of the pump shaft if the water pressure at the barrel is sufficient.

Additions and clarifications.

This method is the most reliable; it allows you to open the valve to the barrel immediately when starting the system and briefly remove the hydraulic elevator from the water, which is necessary when removing water from the premises.

However this method applicable when working with only one G-600 hydraulic elevator, since the diameter of the tank-pump pipe is only 80 mm. and it cannot ensure the operation of two hydraulic elevators.

On currently produced fire trucks, the diameter of the tank-pump pipe is increased, or two pipes with a diameter of 80 mm with separate valves are installed.

In addition, constant monitoring of the water level in the tank with the help of an observer is necessary. Monitoring the water level using level sensors is not operational, which does not allow balancing the flow of water and its consumption. In previous methods of working with a hydraulic elevator, this balance is obtained automatically.

Water harvesting using a hydraulic elevator with vehicle installation at a water source

If there is a water source (hydrant or reservoir), it can be used when cleaning (pumping) water from the premises. To do this, water from the water source is pumped into the pressure line of the hydraulic elevator, and from the hydraulic elevator to the drain.


Rice. 5. Scheme of water harvesting using a hydraulic elevator.

This scheme is more reliable in operation than a closed hydraulic elevator ring and does not require special skills in operation. In some cases, when the pressure in the hydrant is 3 - 4 kgf/cm2, water can be removed without installing the car at the water source, by connecting the pressure line of the hydraulic elevator directly to the fire column.

Maximum use of fire truck power when pumping water

When carrying out emergency rescue operations, as well as in other cases, if the water level in a flooded room is high and it is possible to collect water using suction hoses, then the following scheme for using hydraulic elevators can be recommended.

Rice. 6. Scheme of vehicle operation at maximum power during pumping.

In this case, the volume of pumped water per second when using the PN-40U pump will be about 70-75 l/sec.

Supply of air-mechanical foam without installing a fire truck on a pond

  1. Connect the hose line to the foam generator.
  2. Check that the plug on the pump suction pipe is tightly tightened. Close all valves and taps.
  3. Open the vacuum valve (pull towards yourself) to ensure air escapes from the cavity of the fire pump.
  4. Open the valve from the tank. After water appears in the viewing window of the vacuum valve, close it.
  5. Engage clutch.
  6. Smoothly open the pressure valve into the hose line.

11. Reduce pressure to 1.5 - 2.5 kgf/cm2.

12. Close the valve for supplying foam concentrate from the foam tank.

Failure to perform the operations of washing the foam mixer leads to polymerization and subsequent hardening of the foam concentrate in the dispenser!

  1. Carry out the actions necessary to complete the work.

Supply of air-mechanical foam with installation of a fire truck on a pond

  1. Place the car near a pond in compliance with safety measures.
  2. Attach the suction arms and suction mesh.
  3. Lower the sleeves with the pond mesh. The suction mesh must be lowered at least 300 mm below the water level (to avoid air leakage), but not to the bottom.
  4. Check the closure of the drain valve, valves and plug valve of the foam mixer.
  5. Turn on the power take-off.
  6. Disconnect the clutch from the pump compartment.
  7. Open the vacuum - the valve "pull" and turn on the backlight.
  8. Turn on the gas jet vacuum apparatus.
  9. Use the throttle lever to increase engine speed to maximum. (The characteristic noise of a working HVAC can be heard).
  10. When water appears in the viewing window, wait a short time until air bubbles stop escaping, then close the vacuum valve - away from you.
  11. Reduce engine speed to idle speed.
  12. Engage clutch.
  13. Turn off GVA.
  14. Using the throttle lever, set the water pressure on the pressure gauge to 1-1.5 kgf/cm2.
  15. Open the plug valve of the foam mixer.
  16. Set the dispenser arrow to the number corresponding to the number of foam generators supplied.
  17. Open the valve on the “foam tank - foam mixer” pipeline.
  18. Smoothly open the pressure valve into the hose line.
  19. Increase pressure to 6 kgf/cm2.

After supplying foam, without turning off the pump:

  1. Reduce pressure to 1.5 - 2.5 kgf/cm2.

Close the foam concentrate supply valve from the foam tank.

Foam mixer cleaning operations!

  1. Open the tap on the water tank-foam mixer pipeline.
  2. Turn the handwheel of the foam mixer dispenser in any direction, making at least 4 - 5 full turns.
  3. Make sure that the foam generator comes out pure water no signs of foaming agent.
  4. Close the plug valve of the foam mixer.
  5. Carry out the actions necessary to complete the work.

Additions and clarifications

As you noticed, operations for supplying air-mechanical foam, at the initial stage, are no different from operations for supplying water, with or without installing a fire truck at the water source. But at the same time, when supplying air-mechanical foam, it is necessary to even more carefully control the removal of air from the pump cavity before engaging the clutch.

If there is even a small amount of air in the pump cavity, in the presence of a foaming agent, the pump impeller whips up air-mechanical foam when rotating, which fills the free space.

This can also happen if the flushing of water and foam communications is carried out poorly and the water is not drained from the pump.

IMPORTANT:

The presence of a foam plug in the pump cavity makes it impossible to supply water or foam to extinguish a fire!

It takes considerable time to remove it using a gas-jet vacuum apparatus or by releasing it through pressure pipes.

Video about fire pumps

Loading...